The 9095DS valve is installed at the fill port of a storage tank. Designed for use in pressurized fill systems and requires a tight fill connection. The valve installs in a 2 inch female threaded opening of a low profile tank requiring a high level shut-off. The valve terminates the fill when the product reaches the preset level.
Standard Features
- Designed for fill applications that require a drop tube. (accepts a 1-1/2” male threaded drop tube)
- The valve design allows for full product flow until it reached the shut-off level
- The shut-off height is factory preset and is measured from the bottom of the attachment threads
- Typical flow rate is 26 GPM at 10 PSI pressure drop and 60 GPM at 60 PSI pressure drop
- 10 PSI is the minimum flow requirement for the valve to operate. The valve will not work in gravity filling applications
- Can be retrofitted to existing tanks
- Immediate and cushioned shutoff…full flow up to within 1-2 seconds of closing and no abrupt kickback or line shock when valve closes
- Dry disconnect…after shut off product is allowed to automatically drain from the highest point so fill nozzle can be removed without spilling
- Simple mechanics…minimum moving parts. Shutoff is activated by basic hydraulic principle with no springs, levers or complicated sequence leading to closure
Construction Details
- Adaptor: Anodized aluminum Part A or Part F
- Body: Anodized aluminum
- Float: Nitrophyl-N
- Plunger and dashpot: Brass
- Upper tube and float guard: Aluminum
- Linkage: Stainless steel
- Shut off mechanism: Anodized aluminum
Code Compliance
NFPA 30, 30A, UFC, IFC, PEI/RP 200, and PEI/RP 600