Continuously Monitor Sumps
Where continuous monitoring of the sensor position is required by law, site owners are immediately notified if the sensor has been moved from its proper position at the bottom of the containment sump or dispenser pan.
Alarm conditions are indicated by an audible alarm and displayed message on the Automatic Tank Gauge console and are recorded as a part of the Alarm History Report.
Straight-forward alarm notification upon presence of liquid in your containment area
Detect and pinpoint fluid type in containment areas to allow for smart dispatching
High-grade polymer housing provides enhanced corrosion resistance and fuel compatibility
Increased site uptime in locations where shut down is not required if only water is detected
Single module for two- and three-wire sensors provides greater flexibility for users to monitor multiple sensor types
Delivers extended performance in harsh conditions
Alarm conditions indicated by audible alarm, displayed and printed message
Record of past alarms available as part of Alarm History Report with TLS-4xx series consoles
Robust and rugged screw-in connector allows simplified installation and trouble free inspection.
Fuel Compatibility | Gas, Diesel, Kerosene, Jet Fuel, Aviation Gas, E15, E85, E100, Bio-Diesel 20, Bio-Diesel 100, Green Diesel, DEF, Waste Oil, Motor Oil |
Alarm Notification | Normal: Sensor in Normal State – No liquid detected |
Water Alarm: Water detected at minimum of 1.614” (2.83cm) | |
Fuel Alarm: Fuel detected at minimum of 1.368” (3.47cm) | |
Sensor Out: Sensor not communicating with ATG Console | |
Operating Principle | Magnetostrictive probe with dual floats |
Product Activation Height | Water 1.614” (4.1cm), Fuel 1.368” (3.47cm) |
Operating Temp | -40°C to +60°C |
Dimensions | 2.4” (6.1cm) Diameter; 21.4” (54.4cm) Long (-111 and -211 models), 33.4” (84.8cm) Long (-112 and -212 models) |
Cable Length | 10 feet |